Electromagnetic flowmeter ASAMAG
- Production:
- ASA (Italy)
This series of flowmeters can be used for a wide range of purposes. At the output, digital and analog measurement signals are output, an error of less than 0.5% and a reproducibility of 0.1% of the readings. In addition, ASAMAG is suitable for measuring all types of liquids with conductivity above 5 μS / cm, insensitive to changes in temperature, pressure, density and viscosity of the liquid.
- Measuring range: 0.013 ... 36000 m³ / h;
- Output signal: 4 ... 20 mA, HART;
- Connection: flanged EN1092-1, DIN11851, TriClamp;
- Process temperature: -30 ... + 160 ° C;
- Maximum pressure: 10 bar;
- Accuracy of measurement: ± 0.5%;
- Supply voltage: 220 V DC;
Diameter, mm |
Speed of the flow 0,3 m/s Range of the flow min, m3/g |
Speed of the flow 12 m/s Range of the flow max, m3/g |
Diameter, mm |
Speed of the flow 12 m/s Range of the flow min, m3/g |
Speed of the flow 0,3 m/s Range of the flow max, m3/g |
4 | 0,013 | 0,454 | 200 | 36 | 1140 |
6 | 0,03 | 1,2 | 250 | 54 | 2160 |
15 | 0,18 | 7,2 | 300 | 72 | 2880 |
20 | 0,375 | 15 | 350 | 105 | 4200 |
25 | 0,54 | 21,6 | 400 | 135 | 5400 |
32 | 0,9 | 36 | 450 | 180 | 7200 |
40 | 1,35 | 54 | 500 | 225 | 9000 |
50 | 2,25 | 90 | 600 | 300 | 12000 |
65 | 3,6 | 144 | 700 | 450 | 18000 |
80 | 5,4 | 216 | 800 | 540 | 21600 |
100 | 9 | 360 | 900 | 675 | 27000 |
125 | 13,5 | 540 | 1000 | 900 | 36000 |
150 | 18 | 720 |
Downloads:
Data Sheet
- Типовой лист ASAMAG (pdf, 17`186 Кб)
Instruction manual
- Руководство по эксплуатации ASAMAG (pdf, 1`579 Кб)